Specification

  • ACPower : 110V – 240V AC
  • OperatingVoltage : 24V DC

Standby Power

  • 24VDC(2 12V, 7Ah sealed lead acid battery)
  • Quiescent Current: 55mA

Charging Circuit:

  • ChargingVoltage :28V, ±0.5V
  • ChargingCurrent:0.5A

Zone Circuit:

  • AlarmCurrent:15-35 mA threshold
  • Shortcircuit current:42 mA max
  • Standby current :6.8mA (2.4mA for Detectors)
  • LoopResistance:50Ώ
  • HooterOutput: 1A
  • RelayContact Rating:2Amps @ 24 VDC, 2Amps @ 24VAC (Fire – 2 No’s, Fault – 1 ).
  • Temperature: 50⁰C

 

SKU: TRI-MH-192 Category:

FRMN – 02/04

The FRMN -02/ 04 panel is designed with the latest technology microcontroller. It indicates an alarm for quick remedial action. The system is user-friendly with all standards to ensure ease of use and high reliability.

Features

  • Compact, Sturdy, and Rugged
  • Standby battery backup with built-in
  • Errorfree Fire / Fault (Open Short) status in unambiguous colored LED
  • SwitchMode Power
  • 16X 2 LCD
  • Touch keypad for easy
  • Main, Standby status
  • LowBattery visual warning with audible
  • Zonewise one man walks test
  • Relay output for
  • LampTest
  • Zone isolation facility with loop voltage cut off.
  • ProgrammableKeypad
  • ProgrammableAuto
  • Compatible with all types of conventional

 